| Diesel Generator Set Test Report | |||||||||||||||
| Unit model | LT-W200GF | Diesel engine model | R6105IZLD | Diesel engine brand | Yuchai | Motor model | STF200-1-4 | ||||||||
| manufacturer | Weifang Leiting Power Machinery Co., Ltd. | ||||||||||||||
| Rated capacity KVA | 200 | power factor | 0.8 | Rated frequency Hz | 50 | Rated speed | 1500r/min | ||||||||
| Rated voltage V | 400/380 | Rated current A | 360 | Protection rating | IP21 | ||||||||||
| Relative humidity % | 60 | Ambient temperature °C | 40 | 环境压力 kpa | 100 | ||||||||||
| ※Inspection of diesel engine appearance, markings, and packaging | √ | ※Insulation dielectric strength test | √ | Instrument panel indicator condition detection | |||||||||||
| ※Diesel engine performance testing | √ | ※Room temperature start-up performance test | √ | ※Control panel indicator devices | √ | ※Overspeed protection detection | √ | ||||||||
| insulation testing | Each independent electrical circuit of the diesel engine has a resistance to ground of ≥2 MO. | √ | ※Phase sequence detection: Forward phase sequence | √ | ※High water temperature protection detection | √ | ※Emergency brake detection | √ | |||||||
| Insulation resistance between circuits ≥ 2 MO | √ | ※Overload protection and short circuit protection monitoring | √ | ※Low oil pressure protection detection | √ | ※Battery test | √ | ||||||||
| Electrical performance testing of the unit | |||||||||||||||
| Load rating Power 100% |
Power kW | 电压 V | Current A | Power factor |
Frequency HZ |
Steady-state voltage Deviation o u% |
Frequency drop o fst% |
Frequency fluctuation HZ | Steady-state frequency βf% |
Voltage adjustment range V |
|||||
| UA | UB | UC | 1A | 2A | 3A | maximum value | minimum value | ||||||||
| 0% | 0 | 398 | 399 | 397 | 0 | 0 | 0 | 0.8 | 50.1 | ± 1.62 | 3.8 | 52.1 | 50 | 1.5 | 400/ 380 |
| 25% | 100 | 388 | 385 | 388 | 86 | 90 | 93 | 51 | 3.2 | 52.4 | 50.5 | 1.6 | |||
| 50% | 200 | 392 | 391 | 391 | 176 | 180 | 184 | 50.2 | 2.3 | 51.2 | 50.1 | 1.5 | |||
| 75% | 300 | 390 | 390 | 390 | 264 | 270 | 276 | 50.3 | 1.8 | 52.5 | 50 | 1.5 | |||
| 100% | 400 | 385 | 388 | 386 | 358 | 360 | 366 | 50.1 | 0 | 50.5 | 50.4 | 1.6 | |||
| 75% | 300 | 387 | 387 | 387 | 276 | 270 | 264 | 50.1 | 1.9 | 52.3 | 51.2 | 1.8 | |||
| 50% | 200 | 396 | 965 | 395 | 182 | 180 | 178 | 50 | 2.2 | 52.6 | 50 | 1.7 | |||
| 25% | 100 | 394 | 395 | 393 | 92 | 90 | 88 | 50.6 | 3.2 | 51.2 | 50.5 | 1.6 | |||
| 0% | 0 | 397 | 398 | 396 | 0 | 0 | 0 | 51.9 | 3.9 | 51.9 | 50.6 | 1.4 | |||
| test results | Steady-state voltage deviation o U% | ± 1.61 | Frequency drop ofst% |
4 | |||||||||||
| Voltage adjustment range ≥ ± 4% un | qualified | ||||||||||||||
| Testing conclusions | Approved for shipment | inspector | review | Through | |||||||||||