| Diesel Generator Set Test Report | |||||||||||||||
| Unit model | LT-150GF | Diesel engine model | R6105IZLD | Diesel engine brand | Watkins | Motor model | TZH2-150 | Motor brand | Shanghai Duning | ||||||
| manufacturer | Weifang Leiting Power Machinery Co., Ltd. | ||||||||||||||
| Rated capacity KVA | 188 | power factor | 0.8 | Rated frequency Hz | 50 | Rated speed | 1500r/min | ||||||||
| Rated power kWRated power kW | 150 | Rated voltage V | 400/380 | Rated current A | 270 | Protection rating | IP21 | ||||||||
| Relative humidity % | 60 | Ambient temperature °C | 20 | Rated speed kpa | 100 | ||||||||||
| ※Inspection of diesel engine appearance, markings, and packaging | √ | ※Insulation dielectric strength test | √ | Instrument panel indicator condition detection | |||||||||||
| ※Diesel engine performance testing | √ | ※Room temperature start-up performance test | √ | ※Control panel indicator devices | √ | ※Overspeed protection detection | √ | ||||||||
| insulation testing | Each independent electrical circuit of the diesel engine has a resistance to ground of ≥2 MO. | √ | ※Phase sequence detection: Forward phase sequence | √ | ※High water temperature protection detection | √ | ※Emergency brake detection | √ | |||||||
| Insulation resistance between circuits ≥ 2 MO | √ | ※Overload protection and short circuit protection monitoring | √ | ※Low oil pressure protection detection | √ | ※Battery test | √ | ||||||||
| Electrical performance testing of the unit | |||||||||||||||
| Load rating Power 100% |
Power kW | 电压 V | Current A | Power factor |
Frequency HZ |
Steady-state voltage Deviation o u% |
Frequency drop o fst% |
Frequency fluctuation HZ | Steady-state frequency βf% |
Voltage adjustment range V |
|||||
| UA | UB | UC | 1A | 2A | 3A | maximum value | minimum value | ||||||||
| 0% | 0 | 398 | 397 | 400 | 0 | 0 | 0 | 0.8 | 50 | ± 1.59 | 3.2 | 52.1 | 50 | 1.1 | 400/ 380 |
| 25% | 25 | 395 | 396 | 393 | 66 | 68 | 70 | 52 | 2.9 | 52.2 | 50.5 | 1.4 | |||
| 50% | 50 | 398 | 399 | 390 | 134 | 135 | 138 | 50.2 | 1.9 | 51.1 | 50.1 | 1.7 | |||
| 75% | 75 | 390 | 395 | 397 | 200 | 203 | 206 | 50.4 | 1.1 | 52.4 | 50 | 1.5 | |||
| 100% | 100 | 398 | 399 | 391 | 268 | 270 | 272 | 50.2 | 0 | 50 | 50.4 | 1.6 | |||
| 75% | 75 | 394 | 395 | 397 | 168 | 162 | 158 | 50.1 | 1.3 | 52.3 | 51.2 | 1.3 | |||
| 50% | 50 | 398 | 399 | 390 | 137 | 135 | 132 | 50.2 | 2 | 52.4 | 50 | 1.2 | |||
| 25% | 25 | 395 | 396 | 393 | 66 | 68 | 64 | 50.2 | 2.8 | 51.2 | 50.5 | 1.7 | |||
| 0% | 0 | 398 | 397 | 390 | 0 | 0 | 0 | 51.5 | 3.1 | 51.2 | 50.6 | 1.4 | |||
| test results | Steady-state voltage deviation o U% | ± 1.62 | Frequency drop ofst% |
4 | |||||||||||
| Voltage adjustment range ≥ ± 5% un | qualified | ||||||||||||||
| Testing conclusions | Approved for shipment | inspector | 6 | review | Through | ||||||||||
Tag:
Previous:
Next:
150 kW diesel generator R6110ZLD
Classification